European reference for a low voltage multi-core LSZH power cable with steel wire armour (SWA). Equivalent construction to BS 6724 LSZH armoured cable.. Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. For installation where fire, smoke emission and toxicfumes create a potential
| Voltage Rating Uo/U | 0.6/1kV |
| Conductor | Class 2 stranded copper conductor |
| Insulation | XLPE (Cross-Linked Polyethylene) |
| Bedding | LSZH (Low Smoke Zero Halogen) |
| Armour | SWA (Steel Wire Armour) |
| Sheath | LSZH (Low Smoke Zero Halogen) |
| Temperature Rating | Fixed: -20°C to +90°C |
| Minimum Bending Radius | 1.5mm² to 16mm2 – Fixed: 6 x overall diameter 25mm2 and above – Fixed: 8 x overall diameter |
| Standards | BS 6724, IEC/EN 60228, EN 50267-2-1, IEC/EN 60502-1, Flame Retardant according to IEC/EN 60332-1-2, IEC/EN 60332-3-24 Cat C Low Smoke Zero Halogen according to IEC/EN 60754-1/2, IEC/EN 61034-1/2 |
| Suitability | For underground (direct buried), outdoor and internal applications. LSZH sheathing for where fire, smoke emission and toxic fumes create a potential threat to life and equipment. |
N2XRH cable uses Low Smoke Zero Halogen compounds (also known as HFFR – halogen free flame retardant) and is comparable to the BS6724 cable.