LiYCY is a flexible, multi-conductor, screened data and control cable designed for low-voltage signal transmission in environments with elevated electromagnetic interference (EMI). The designation follows German VDE conventions: Li indicates Class 5 fine-stranded annealed copper conductors (IEC 60228 / VDE 0295), the first Y denotes PVC core insulation, C signifies an overall tinned copper braid screen, and the final Y indicates a PVC outer sheath. Typical rated voltage is 250 V (sections ≤ 0.25–0.34 mm²) or 300/500 V (larger sections). Operating temperature ranges from –30 °C to +70/80 °C (fixed) and –5 °C to +70/80 °C (flexing). The cable is engineered primarily for instrumentation, industrial automation, computer systems, and measurement circuits where the copper braid provides EMC protection. It is not intended for power distribution or outdoor installation.

Technical Parameter Comparison Matrix
| Parameter | LiYCY (Screened) | LiYY (Unscreened) | Typical Standards / Notes |
|---|---|---|---|
| Screen | Overall tinned copper braid (≈70–85 % coverage) | None | EMC performance critical for LiYCY |
| Rated Voltage | 250 V (≤0.25–0.34 mm²); 300/500 V (≥0.5 mm²) | Same | Not for power installation |
| Conductor | Class 5 fine-stranded bare copper | Class 5 fine-stranded bare copper | IEC 60228 / VDE 0295 |
| Insulation | PVC (TI2 / EN 50363) | PVC | DIN 47100 colour coding |
| Outer Sheath | PVC (grey, RAL 7032 / 7001) | PVC | Flame retardant per IEC 60332-1 |
| Temperature (Fixed) | –30 °C to +70/80 °C | –30/–40 °C to +70/80 °C | Manufacturer-dependent slight variations |
| Temperature (Flexing) | –5 °C to +70/80 °C | –5 °C to +70 °C | — |
| Min. Bending Radius | Fixed 5–10× OD; Flexing 10–15× OD | Fixed 4–6× OD; Flexing 10× OD | Higher for screened versions |
| Capacitance (approx.) | Core/core ≈120 nF/km; Core/screen higher | Core/core ≈120 nF/km | Relevant for signal integrity |
| Typical Applications | Sensors, instrumentation, EMC-critical data | Internal cabinet wiring, low-EMI zones | — |
Cable Construction and Materials
LiYCY construction begins with annealed copper conductors of Class 5 flexibility (fine wire strands per IEC 60228). Each core is insulated with special PVC compound and colour-coded according to DIN 47100 without colour repetition. Cores are stranded in layers with optimal lay length, wrapped with transparent polyester foil, and covered by a tinned copper braid screen offering high optical coverage (typically 70–85 %). The outer sheath is extruded PVC, normally grey (RAL 7032 or 7001), providing mechanical protection and flame-retardant performance conforming to IEC 60332-1 / EN 60332-1-2.
Key material properties include:
- High insulation resistance (typically ≥100–200 MΩ·km)
- Mutual capacitance kept low to preserve signal quality
- Flame-retardant and self-extinguishing behaviour
- RoHS and often CPR (EN 50575) compliance
Electrical Performance Characteristics
Nominal voltage is section-dependent: smaller conductors (0.14–0.34 mm²) are rated around 250 V, while sections ≥0.5 mm² commonly carry 300/500 V. Test voltages are typically 1.2–2.0 kV (core-to-core) and lower for core-to-screen. Inductance is approximately 0.65 mH/km. The copper braid significantly reduces coupling of external electromagnetic fields, making the cable suitable for analogue and digital signal lines running near power circuits, variable-frequency drives, or industrial machinery.

Application Domains and Limitations
LiYCY is specified for:
- Industrial automation and process control
- Computer and office equipment interconnects
- Measurement and instrumentation circuits
- Sensor and encoder connections requiring EMC integrity
- Environments with moderate mechanical stress and free movement (no continuous tensile load)
It is not recommended for outdoor exposure, permanent immersion, or power distribution circuits. Installation should respect the stated bending radii and temperature limits. Screen termination must be performed with low-impedance, 360° connection methods to realise the full EMC benefit.
Standards Compliance and Identification
Primary references include VDE 0812 (construction basis), IEC 60228 (conductors), DIN 47100 (core identification), EN 50363 (insulation and sheath compounds), and IEC 60332-1 (flame performance). Many manufacturers also declare CE marking under the Low Voltage Directive and CPR classification. The type designation LiYCY itself conveys the essential construction details to specifying engineers and purchasing teams across European and international markets.
Selection Guidance Relative to Related Types
When EMC protection is required, LiYCY is preferred over unscreened LiYY. For higher mechanical robustness or individual pair screening, variants such as LiYCY-CY or twisted-pair versions (LiYCY-TP / LiYCY-P) may be evaluated. Voltage, temperature, and movement class must always be verified against the specific manufacturer’s data sheet, as minor differences exist between producers while the fundamental LiYCY construction remains consistent.