PVC insulated and sheathed power cable standard and parameter data

PVC insulated and sheathed power cable Execution standard

XLPE insulated power cable performance conforms to GB12706.2-1991 equivalent IEC60502-1997, flame retardant performance conforms to GB12666.5-1990 equivalent IEC332-1992. (Not applicable to non-flame retardant cables)

PVC insulated and sheathed power cable Use characteristics

Use characteristics: the rated working voltage of the cable U0/U 0.6/1KV;

Test voltage (duration ≤ 5min) 3.5KV;

Cable conductor long-term working temperature ≤ 70 ° C;

When short circuit (duration ≤ 5s) cable conductor temperature ≤ 160 ° C;

When laying the cable, the smaller bending radius single core cable should be ≥ 10 times the outer diameter of the cable, and the armored cable should be ≥ 12 times the outer diameter of the cable. When the cable is laid, the ambient temperature is ≥ 0 °C. When it is lower than 0 °C, the temperature is pre-heated, and it is not restricted by the drop when laying.

PVC insulated and sheathed power cable Technical indicators

Technical indicators: The DC resistance of the conductor is the same as that of the cross-section cable of the same cross section; the insulation resistance of the finished cable is converted to 20 °C ≥ 36.7 MΩ.km; at room temperature, it is subjected to AC 50Hz, 3.5KV 5min test.


PVC insulated and sheathed power cable parameter data

PVC insulated PVC sheathed power cable OD

Cross-sectional areacore
12343+153+24+1
1.56.610.611.016.0
2.57.011.511.917.0
47.913.613.814.814.616.015.519.0
68.514.514.916.016.017.017.523.5
109.716.917.819.318.919.019.028.0
1610.718.919.921.821.524.023.031.0
2512.422.824.626.525.629.027.032.5
3513.625.226.829.227.933.028.036.0
5015.825.125.433.728.733.032.541.5
7017.627.027.734..832.536.036.045.0
9520.728.832.139.637.342.041.049.0
12022.031.235.142.939.945.045.054.0
15024.034.738.947.844.650.048.061.0
18526..537.542.953.050.355.053.067.0