N2XRH Cable: Construction, Standards, and Applications of XLPE-Insulated SWA LSZH Low Voltage Power Cable

N2XRH Combines XLPE Insulation, Steel Wire Armour, and LSZH Sheath for Mechanically Protected Fire-Safe LV Power Distribution

N2XRH is a 0.6/1 kV low-voltage power cable featuring Class 2 stranded copper conductors, XLPE insulation, galvanized steel wire armour (SWA), and a Low Smoke Zero Halogen (LSZH) outer sheath. It corresponds closely to the British Standard BS 6724 construction and complies with IEC 60502-1. The cable delivers a continuous conductor operating temperature of 90°C and short-circuit rating of 250°C, while the LSZH sheath minimises smoke density and eliminates halogen acid gas emission. The steel wire armour provides high mechanical protection, making N2XRH suitable for underground, outdoor, industrial, and public-building installations where both mechanical robustness and enhanced fire safety are required.

Technical Comparison Matrix: N2XRH vs Related Cable Types

ParameterN2XRHN2XRYN2XH (unarmoured)Equivalent Standard
Voltage rating0.6/1 kV0.6/1 kV0.6/1 kVIEC 60502-1
ConductorClass 2 stranded copperClass 2 stranded copperClass 2 stranded copperIEC 60228
InsulationXLPEXLPEXLPEIEC 60502-1
Continuous operating temperature90°C90°C90°CIEC 60502-1
Short-circuit temperature250°C250°C250°CIEC 60502-1
BeddingLSZHPVCLSZH (typical)—
ArmourGalvanized steel wire (SWA)Galvanized steel wire (SWA)None—
Outer sheathLSZHPVCLSZH—
Smoke densityLow (IEC 61034)HighLow (IEC 61034)IEC 61034
Halogen acid gas emissionNegligible (IEC 60754)HighNegligible (IEC 60754)IEC 60754
Mechanical protectionHighHighLow—
Typical British equivalentBS 6724BS 5467——

Cable Designation Breakdown

In the European/VDE-style coding system:

  • N — Standard construction with copper conductors
  • 2X — Cross-linked polyethylene (XLPE) insulation
  • R — Round steel wire armour (galvanized)
  • H — Halogen-free (LSZH / HFFR) outer sheath

This designation clearly distinguishes N2XRH from N2XRY (PVC-sheathed armoured version) and from unarmoured N2XH cables.

Construction Details

A standard multi-core N2XRH cable consists of the following layers:

  • Conductor: Annealed copper, Class 2 stranded (IEC 60228)
  • Insulation: XLPE, rated for 90°C continuous operation
  • Core assembly: Insulated cores laid up with LSZH fillers
  • Bedding / Inner covering: Extruded LSZH compound
  • Armour: Single layer of galvanized round steel wires (SWA)
  • Outer sheath: Extruded LSZH compound (typically black)

Single-core versions normally use aluminium wire armour (AWA) to avoid magnetic losses. Core identification follows standard colour coding or numbered cores according to the applicable national or project specification.

Fire Performance Characteristics

N2XRH is designed for installations where smoke and corrosive gas emission must be limited:

  • Flame retardant to IEC 60332-1-2 (single cable) and IEC 60332-3 Category C (bunched cables)
  • Low smoke emission to IEC 61034-1/2
  • Halogen-free and low corrosivity to IEC 60754-1/2

These properties make the cable suitable for public buildings, high-rise structures, tunnels, data centres, hospitals, and other areas where escape route visibility and protection of sensitive equipment are critical. Note that standard N2XRH provides halogen-free and low-smoke performance; circuit-integrity (fire-resistant) versions require additional mica tape and specific testing (e.g., FE180 / IEC 60331) and are designated accordingly (e.g., N2XRH-J FE180).

Standards and Compliance

  • IEC 60502-1: Primary construction and testing standard for extruded insulation power cables
  • BS 6724: Closest British Standard equivalent (armoured cables with thermosetting insulation and LSZH sheath)
  • IEC 60228: Conductor classification
  • IEC 60332 series: Flame propagation
  • IEC 61034: Smoke density
  • IEC 60754: Halogen acid gas emission and acidity
  • CPR (EN 50575) classification applies according to the specific manufacturer’s declaration

Application Areas

N2XRH is selected when both mechanical protection and improved fire safety are required:

  • Underground and direct-buried power distribution
  • Outdoor and industrial installations exposed to mechanical risk
  • Public and commercial buildings with strict smoke and toxicity requirements
  • Cable routes in tunnels, mass transit systems, and high-occupancy structures
  • Power networks where the armour can also serve as a protective earth path when properly bonded

Installation Considerations

  • Minimum bending radius is typically 6× to 8× overall diameter for smaller sizes and 8× to 12× for larger sizes (confirm with manufacturer data)
  • Suitable for indoor, outdoor, duct, and direct burial installation
  • Requires appropriate SWA glands to maintain earth continuity and mechanical retention
  • Operating temperature range for fixed installation is commonly –20°C to +90°C

Selection Guidance

Choose N2XRH when the installation demands:

  • Steel wire armour for mechanical protection, and
  • LSZH performance to limit smoke and halogen acid gases

Choose N2XRY when mechanical protection is required but low-smoke/zero-halogen performance is not specified.
Choose unarmoured N2XH when mechanical risk is low and only halogen-free performance is needed.

N2XRH provides a robust, standards-compliant solution for 0.6/1 kV power distribution circuits that must simultaneously withstand mechanical stress and meet elevated fire-safety requirements. Correct specification of conductor size, number of cores, and compliance with IEC 60502-1 / BS 6724 ensures reliable long-term performance under the thermal, mechanical, and environmental conditions of the installation.