What Are the Key Advantages of LSZH Sheathed Armoured Cables in Industrial and Public Buildings?

LSZH sheathed armoured cables (such as NA2XRH and N2XRH) combine XLPE insulation, steel-wire or steel-tape armour, and a Low Smoke Zero Halogen outer sheath. Rated 0.6/1 kV to IEC 60502-1, these cables maintain a continuous conductor temperature of 90 °C and short-circuit rating of 250 °C. Their primary advantages over standard PVC-sheathed armoured cables are significantly reduced smoke density, absence of corrosive halogen gases during fire, and improved safety for people and equipment in enclosed or high-occupancy spaces. They are the preferred choice when fire safety regulations or project risk assessments mandate low-smoke and halogen-free performance.

Technical Parameter Comparison Matrix: LSZH vs PVC Sheathed Armoured Cables

ParameterLSZH Sheathed Armoured (e.g. NA2XRH / N2XRH)PVC Sheathed Armoured (e.g. NA2XRY / N2XRY)
InsulationXLPEXLPE
ArmourSWA or DSTASWA or DSTA
Outer SheathLSZH (Low Smoke Zero Halogen)PVC
Continuous Operating Temperature90 °C90 °C
Short-Circuit Temperature250 °C250 °C
Smoke Density (IEC 61034)Very lowHigh
Halogen Acid Gas Emission (IEC 60754)ZeroHigh (HCl release)
Flame PropagationImproved (often meets IEC 60332-3)Standard
Corrosivity of Combustion GasesNegligibleHigh
Typical ApplicationsPublic buildings, tunnels, data centres, industrial plants with high safety requirementsGeneral industrial and outdoor use
StandardIEC 60502-1 + IEC 61034 / IEC 60754IEC 60502-1

Fire Safety Performance

When exposed to fire, conventional PVC sheaths release large volumes of dense black smoke and corrosive hydrogen chloride (HCl) gas. LSZH compounds are formulated from halogen-free polymers that produce minimal smoke and no halogenated acids. This greatly improves visibility for evacuation, reduces toxicity, and protects sensitive electronic equipment and metal structures from corrosion after a fire incident.

Mechanical and Electrical Continuity

The armour (SWA or DSTA) and XLPE insulation remain unchanged, so mechanical protection, tensile strength, and electrical performance are identical to the equivalent PVC-sheathed versions. Current-carrying capacity, voltage rating, and short-circuit withstand capability are therefore the same.

Typical Application Scenarios

LSZH sheathed armoured cables are strongly recommended for:

  • Hospitals, schools, airports, and shopping centres
  • Underground tunnels and metro systems
  • Data centres and control rooms
  • High-rise buildings and confined industrial spaces
  • Any installation where local fire codes or insurance requirements specify low-smoke and zero-halogen materials

Material and Installation Considerations

LSZH sheaths are generally slightly stiffer and more expensive than PVC. Minimum bending radii should be observed carefully during installation. Cable glands and accessories must be compatible with LSZH materials to maintain the overall fire-performance rating of the system.

Compliance Notes

In addition to IEC 60502-1, LSZH cables are typically tested to:

  • IEC 61034 (smoke density)
  • IEC 60754-1 / -2 (halogen acid gas and acidity)
  • IEC 60332-1 or IEC 60332-3 (flame propagation)

Project specifications should clearly state the required fire-performance test levels.

LSZH sheathed armoured cables deliver the same electrical and mechanical performance as conventional PVC-sheathed armoured cables while providing critical fire-safety advantages—low smoke emission and zero halogen release. They should be specified whenever human safety, equipment protection, and regulatory compliance in enclosed or public spaces take priority over initial material cost.