What Is the Difference Between H05V-K / H07V-K and H05Z-K / H07Z-K Flexible Cables?

H05V-K and H07V-K are PVC-insulated flexible single-core cables rated 300/500 V and 450/750 V respectively, designed for internal wiring of equipment and control panels. H05Z-K and H07Z-K are the Low Smoke Zero Halogen (LSZH) equivalents with the same voltage ratings and flexible Class 5 copper conductors. The key difference lies in the insulation material: PVC versus halogen-free cross-linked or thermoplastic compounds. H05Z-K / H07Z-K should be selected when fire safety, low smoke emission, and zero halogen release are required by regulations or project specifications.

Technical Parameter Comparison Matrix

ParameterH05V-K / H07V-KH05Z-K / H07Z-K
Insulation MaterialPVCLSZH (halogen-free)
ConductorFlexible annealed copper, Class 5Flexible annealed copper, Class 5
Rated Voltage (H05)300/500 V300/500 V
Rated Voltage (H07)450/750 V450/750 V
Continuous Operating Temperature70 °C90 °C (typical for many LSZH compounds)
Smoke EmissionHighVery low (IEC 61034)
Halogen Acid GasYes (HCl)Zero (IEC 60754)
FlexibilityExcellentExcellent
Flame RetardanceStandardImproved
Typical StandardsEN 50525-2-31EN 50525-3-41
Common ApplicationsGeneral equipment wiring, control panelsPublic buildings, data centres, ships, tunnels

Construction and Material Differences

Both cable families use finely stranded Class 5 copper conductors for high flexibility.
H05V-K / H07V-K employ conventional PVC insulation, which is cost-effective and easy to strip.
H05Z-K / H07Z-K use halogen-free insulation compounds that do not release corrosive or toxic halogen gases when exposed to fire and produce significantly less smoke.

Fire Performance and Safety

PVC-insulated cables release dense smoke and hydrogen chloride gas during combustion. LSZH versions (H05Z-K / H07Z-K) comply with smoke density and halogen-free requirements of IEC 61034 and IEC 60754, making them suitable for enclosed spaces where evacuation visibility and equipment protection are critical.

Application Selection Guidelines

Choose H05V-K / H07V-K when:

  • Cost is the primary consideration
  • The installation is in well-ventilated or non-critical areas
  • No specific low-smoke or halogen-free requirement exists

Choose H05Z-K / H07Z-K when:

  • Local fire codes or client specifications mandate LSZH materials
  • Cables are installed in public buildings, hospitals, data centres, railway vehicles, or ships
  • Protection of sensitive electronic equipment from corrosive combustion gases is required

Installation Notes

Both types are intended for fixed installation inside equipment, switchgear, and control cabinets. They are not designed for direct burial or outdoor exposure without additional protection. Minimum bending radii and maximum operating temperatures must be observed according to the manufacturer’s datasheet.

Summary: H05V-K / H07V-K cables offer an economical PVC solution for general flexible wiring. H05Z-K / H07Z-K cables provide equivalent electrical performance with superior fire-safety characteristics and should be specified whenever low smoke and zero halogen performance are required.