LSZH sheathed armoured cables (such as NA2XRH and N2XRH) combine XLPE insulation, steel-wire or steel-tape armour, and a Low Smoke Zero Halogen outer sheath. Rated 0.6/1 kV to IEC 60502-1, these cables maintain a continuous conductor temperature of 90 °C and short-circuit rating of 250 °C. Their primary advantages over standard PVC-sheathed armoured cables are significantly reduced smoke density, absence of corrosive halogen gases during fire, and improved safety for people and equipment in enclosed or high-occupancy spaces. They are the preferred choice when fire safety regulations or project risk assessments mandate low-smoke and halogen-free performance.

Technical Parameter Comparison Matrix: LSZH vs PVC Sheathed Armoured Cables
| Parameter | LSZH Sheathed Armoured (e.g. NA2XRH / N2XRH) | PVC Sheathed Armoured (e.g. NA2XRY / N2XRY) |
|---|---|---|
| Insulation | XLPE | XLPE |
| Armour | SWA or DSTA | SWA or DSTA |
| Outer Sheath | LSZH (Low Smoke Zero Halogen) | PVC |
| Continuous Operating Temperature | 90 °C | 90 °C |
| Short-Circuit Temperature | 250 °C | 250 °C |
| Smoke Density (IEC 61034) | Very low | High |
| Halogen Acid Gas Emission (IEC 60754) | Zero | High (HCl release) |
| Flame Propagation | Improved (often meets IEC 60332-3) | Standard |
| Corrosivity of Combustion Gases | Negligible | High |
| Typical Applications | Public buildings, tunnels, data centres, industrial plants with high safety requirements | General industrial and outdoor use |
| Standard | IEC 60502-1 + IEC 61034 / IEC 60754 | IEC 60502-1 |
Fire Safety Performance
When exposed to fire, conventional PVC sheaths release large volumes of dense black smoke and corrosive hydrogen chloride (HCl) gas. LSZH compounds are formulated from halogen-free polymers that produce minimal smoke and no halogenated acids. This greatly improves visibility for evacuation, reduces toxicity, and protects sensitive electronic equipment and metal structures from corrosion after a fire incident.
Mechanical and Electrical Continuity
The armour (SWA or DSTA) and XLPE insulation remain unchanged, so mechanical protection, tensile strength, and electrical performance are identical to the equivalent PVC-sheathed versions. Current-carrying capacity, voltage rating, and short-circuit withstand capability are therefore the same.
Typical Application Scenarios
LSZH sheathed armoured cables are strongly recommended for:
- Hospitals, schools, airports, and shopping centres
- Underground tunnels and metro systems
- Data centres and control rooms
- High-rise buildings and confined industrial spaces
- Any installation where local fire codes or insurance requirements specify low-smoke and zero-halogen materials

Material and Installation Considerations
LSZH sheaths are generally slightly stiffer and more expensive than PVC. Minimum bending radii should be observed carefully during installation. Cable glands and accessories must be compatible with LSZH materials to maintain the overall fire-performance rating of the system.
Compliance Notes
In addition to IEC 60502-1, LSZH cables are typically tested to:
- IEC 61034 (smoke density)
- IEC 60754-1 / -2 (halogen acid gas and acidity)
- IEC 60332-1 or IEC 60332-3 (flame propagation)
Project specifications should clearly state the required fire-performance test levels.
LSZH sheathed armoured cables deliver the same electrical and mechanical performance as conventional PVC-sheathed armoured cables while providing critical fire-safety advantages—low smoke emission and zero halogen release. They should be specified whenever human safety, equipment protection, and regulatory compliance in enclosed or public spaces take priority over initial material cost.