H05V-K and H07V-K are PVC-insulated flexible single-core cables rated 300/500 V and 450/750 V respectively, designed for internal wiring of equipment and control panels. H05Z-K and H07Z-K are the Low Smoke Zero Halogen (LSZH) equivalents with the same voltage ratings and flexible Class 5 copper conductors. The key difference lies in the insulation material: PVC versus halogen-free cross-linked or thermoplastic compounds. H05Z-K / H07Z-K should be selected when fire safety, low smoke emission, and zero halogen release are required by regulations or project specifications.

Technical Parameter Comparison Matrix
| Parameter | H05V-K / H07V-K | H05Z-K / H07Z-K |
|---|---|---|
| Insulation Material | PVC | LSZH (halogen-free) |
| Conductor | Flexible annealed copper, Class 5 | Flexible annealed copper, Class 5 |
| Rated Voltage (H05) | 300/500 V | 300/500 V |
| Rated Voltage (H07) | 450/750 V | 450/750 V |
| Continuous Operating Temperature | 70 °C | 90 °C (typical for many LSZH compounds) |
| Smoke Emission | High | Very low (IEC 61034) |
| Halogen Acid Gas | Yes (HCl) | Zero (IEC 60754) |
| Flexibility | Excellent | Excellent |
| Flame Retardance | Standard | Improved |
| Typical Standards | EN 50525-2-31 | EN 50525-3-41 |
| Common Applications | General equipment wiring, control panels | Public buildings, data centres, ships, tunnels |
Construction and Material Differences
Both cable families use finely stranded Class 5 copper conductors for high flexibility.
H05V-K / H07V-K employ conventional PVC insulation, which is cost-effective and easy to strip.
H05Z-K / H07Z-K use halogen-free insulation compounds that do not release corrosive or toxic halogen gases when exposed to fire and produce significantly less smoke.

Fire Performance and Safety
PVC-insulated cables release dense smoke and hydrogen chloride gas during combustion. LSZH versions (H05Z-K / H07Z-K) comply with smoke density and halogen-free requirements of IEC 61034 and IEC 60754, making them suitable for enclosed spaces where evacuation visibility and equipment protection are critical.
Application Selection Guidelines
Choose H05V-K / H07V-K when:
- Cost is the primary consideration
- The installation is in well-ventilated or non-critical areas
- No specific low-smoke or halogen-free requirement exists
Choose H05Z-K / H07Z-K when:
- Local fire codes or client specifications mandate LSZH materials
- Cables are installed in public buildings, hospitals, data centres, railway vehicles, or ships
- Protection of sensitive electronic equipment from corrosive combustion gases is required
Installation Notes
Both types are intended for fixed installation inside equipment, switchgear, and control cabinets. They are not designed for direct burial or outdoor exposure without additional protection. Minimum bending radii and maximum operating temperatures must be observed according to the manufacturer’s datasheet.
Summary: H05V-K / H07V-K cables offer an economical PVC solution for general flexible wiring. H05Z-K / H07Z-K cables provide equivalent electrical performance with superior fire-safety characteristics and should be specified whenever low smoke and zero halogen performance are required.